MODEL | STANDARD | Dual chord |
Nature of equipment | Fixed | Fixed |
Measurement on pipe under load | No | No |
Flow measurement on open channel | Yes | Yes |
Width of channel/river | Up to 50m in clear water | Up to 50m in clear water |
Inputs/Outputs | › 2 current outputs, 4-20mA (1000Ω galvanically isolated as a passive output/impedance of 150Ω as an active output) › 2 static relay outputs (100V - 100mA - 10VA max) | › 2 current outputs, 4-20mA (1000Ω galvanically isolated as a passive output/impedance of 150Ω as an active output) › 2 static relay outputs (100V - 100mA - 10VA max) |
Use | Speed measurement with one (speed) chord | Speed measurement with two (speed) chords |
Single or dual channel | Single channel | Single channel |
Single or dual chord | Single chord | Dual chord |
Display | › A lphanumeric (2 lines x 16 characters) › B acklit LCD screen with time delay feature | › A lphanumeric (2 lines x 16 characters) › B acklit LCD screen with time delay feature |
Set-up | › Quick and simple using 4-key touch pad - or - via dedicated software supplied › Possible to include an access code | › Quick and simple using 4-key touch pad - or - via dedicated software supplied › Possible to include an access code |
Operating system | Windows for set-up and saving application data | Windows for set-up and saving application data |
7 languages | French • English • German • Portuguese • Spanish • Italian • Polish | French • English • German • Portuguese • Spanish • Italian • Polish |
Serial link | RS232 or RS485 to JBUS/MODBUS protocol • 9600 Bauds | RS232 or RS485 to JBUS/MODBUS protocol • 9600 Bauds |
Accessory (optional) | 1 RS232 to USB converter link cable | 1 RS232 to USB converter link cable |
Basic power supply | Low voltage: 9-36V dc or 7-25V ac (5VA ) | Low voltage: 9-36V dc or 7-25V ac (5VA ) |
Optional power supply | 18-72V dc or 90-230V ac (5VA ) | 18-72V dc or 90-230V ac (5VA ) |
Enclosure | Cast aluminium & epoxy paint • 1.5kg • 237 x 108 x 79mm | Cast aluminium & epoxy paint • 1.5kg • 237 x 108 x 79mm |
Protection | IP 67 | IP 67 |
Temperature range | For use from 0°C to 50°C | For use from 0°C to 50°C |